SECTION I. GENERAL DESCRIPTION
Contractor shall furnish and install the SD1-550
self-contained, self-cleaning collector and side-draft dust control panel
per plans. The unit shall be an SD1- 550 as manufactured by USA or
approved equal.
Each unit shall consist of a cabinet style filtration module, motor blower
module, on/off control, compressed air manifolds, 1” diaphragm valves
attached to convergent/divergent blast nozzles. A 58”x58” baffled face
dust control panel fitted with 13 ply spark arrestance panels complete the
assembly. The SD1-550 shall be completely factory assembed as a self
contained unit. Each unit shall be neatly finished with hammer style,
powder coat, thoroughly tested and properly packaged for shipping. Both
filtration and blower modules must be the product of the same manufacturer
to insure undivided responsibility and simplified servicing. The collector
precision sheetmetal fabriction shall be fabricated in an ISO-9000
compliant facility and the complete packaged unit shall bear the ETL/CSA
label.
SECTION II. COLLECTOR CAPACITY RATING
The capacity of each unit at nominal rating
shall be to produce at least 4000 actual cubic feet per minute. Free air
rating shall be at least 5500 cubic feet per minute airflow with new
cartridges. Fan wheel is a 15” airfoil, backward inclined,
non-overloading high efficiency spark resistant type. Motor shall be; 5
HP, ODP, 3450 RPM, 208/230/460/3/60.
The primary filter cartridges are to be 100% spun bond polyester with
engineered dimpled pleats (stops bridging during pulsing). Hydro
Oleophobic (HO) treated polyester 80/20 cell/poly blend may also be used
depending upon the application specification. The cartridges are 30”Hx
18”OD x14”ID. Spun bond polyester media is 99.9% efficient at .3
micron particulate size.
SECTION III. COLLECTOR DESIGN AND SIZE
Collector shall be of side-draft design with the
baffled side-draft panel serving also as the filter cartridge and dust
tray access door. The side-draft panel consists of 5 vertically arranged
58”x6” baffle slats with 1” 45° wings arranged 1 1/2” apart. A
second row of 6 baffle slats is arranged back to back and staggered to
create the airflow “eddy” sufficient for spark attenuation. A third
line of tortuous path spark arrestance shall consist of (4) 24”x24”x2”
thick panels with 10 ply of expanded aluminum mesh and 3 ply of tight
woven steel screen interspersed. The aluminum mesh filters are rated to
achieve 100% spark arrestance up to 700 FPM per 24”x24”x2” panel.
Air enters the baffled side draft panels at 650 feet per minute face
velocity.
The filter cartridges rest on a sloped
blower transition plenum. Metal clamp down compression strips secure the
cartridges to blower plenum. At the junction of the transition plenum and
the base housing panel are four removable dust trays.
A minimum of four clear inches of space shall exist between the cartridge
and the housing walls on three sides (better air flow distribution). A
minimum of eight inches of space shall separate the cartridges (limit
cross blasting of particulate).
The main collector housing will have a minimum of 25 Sq. ft. of 1” thick
class one acoustical lining. Total blower noise shall not exceed 78 DBA at
3ft. on the discharge side and 68 DBA at 3 ft. on the side-draft
panel/access door side.
The collector will make use of standard
convection fins in the side panels to enhance heat transfer away from the
motor.
The Motor/Blower frame, panels and housing will be 12 ga. welded steel
construction. The side panels are situated to provide access to two sides
of the fan wheel motor, and electrical fittings.
|
The filter module housing and blower plenums shall be of 12 ga. welded
steel construction with a single hinged side-draft panel that is fitted
with a compression gasket and will allow access to both cartridges and all
four dust trays.
The reverse pulse assembly, consisting
of the air manifolds, 1” diaphragm valves and diverging/converging blast
nozzle shall be mounted to the sides and beneath the blower plenum with a
diaphragm valve and blast nozzles directly below each cartridge.
SECTION IV. CONTROLS AND FITTINGS.
All junctions, connectors, leads, strain relief grommets, wiring and
components are ETL/CSA recognized components.
Blower/Motor control shall be of the on/off operation type, and may
include 115VAC stepdown transformer for integral high intensity GSL Hood
lighting. The motor starter shall be equipped with thermal overload and
under voltage protection. Motor/Blower control box shall be panel mounted
and so located on collector to provide ease of servicing and use.
SECTION V. FILTER MODULE CONTROLS
A manual reverse pulse controller shall be
installed behind the filter module and shall be of on/off type. An
optional reverse pulse controller shall provide an automatic cleaning
sequence of the filter cartridges. The cleaning process with the optional
control is activated when the @ΔP set point
is exceeded by the actual @ΔP value. When
the set point is exceeded the controller activates the electric diaphragm
valves according to a preset, constant pulse and interval time setting. A
digital display shall indicate the preset filter module @ΔP
set point value. The optional controller will also perform a final
cleaning sequence upon shut down of the system.
SECTION VI. TEST
A. QC of the collector shall include
physical inspection of the following:
1. Finish
2. Motor Mounts
3. Shaft
4. Key Way
5. Fan and Cone Alignment
Followed by a trial power-up to test the
reverse pulse controller, motor/blower control, and direction of fan
rotation. Finally a test of the acoustical lining for adhesive performance
and a physical inspection of the primary filter cartridge for shipping
damage, pleat seal, gasket seal, tears and/or pin holes.
SECTION VII. OWNER’S MANUAL
A. Instructions for installation, operation and
maintenance of the collector shall be
contained in the owner’s manual provided
with each collector unit.
B. A wiring diagram corresponding to the
collector shall be included in the owner’s manual.
Instructions for owner’s the reverse pulse
controller and the corresponding wiring diagram
shall be contained in the owner’s manual pro-
vided with each collector unit.
SECTION VIII. WARRANTY
The collector shall have a one year (12
month) material and workmanship warranty. All other components are covered
by a one year manufacturers (12 month) warranty. |